Last review: 02/27/2012
Conservation Ideas - Building Operator
- Verify outside air (OSA) dampers are closed during
unoccupied hours, including morning warm-up periods. Fresh air
is critical, but heating OSA when it is not needed increases
energy costs. Typically 15 CFM of OSA/person is standard.
- Confirm the amount of outside air matches occupant load. An
inexpensive improvement is CO2 or VOC sensors to match expensive
outside air to occupant load.
- Be sure damper motors are operating properly.
- Confirm that the OSA economizer is functioning
properly and using free cooling when OSA temperature is below
about 65 degrees. Most buildings are in cooling when the outside
air temperature is above 55 degrees. The core of buildings over
20,000 square feet are almost always in cooling, even during the
winter heating season.
- Check to make sure exhaust fans are running only
during occupied times. Check that dampers on exhaust fans close
when the fan is not operating. Adjust fan belt tension.
- Inspect control schedules to heat only sections of
the building as needed. For electric space heating, stagger
start times to help reduce demand charges.
- Monitor stack temperatures on fossil fuel boilers. If
the stack temperature is more than 400 degrees F above the
boiler room temperature, schedule the boiler for a tune-up.
- Turn off circulation pumps during unoccupied times if
no freeze conditions exist. Heat loss from poorly insulated
pipes can be a major loss of energy. Check hot water insulation
levels.
- Install controls to automatically reset hot and cold
deck temperatures based on the space demand. (Usually
inexpensive, controls can save 10% of space conditioning costs,
and typically increases employee comfort).
- Check multiple parallel chillers for light load
operation. Check chillers for cycling and use the smallest
chiller.
- Verify that the building control system is going into
night setback during unoccupied hours. Just because it’s a
computer controlled system doesn’t mean it is working right!
- Make sure that simultaneous heating and cooling does not
occur—is there a stuck valve?
- Confirm that your adjustable speed drives (ASD) are
not running constantly at 100% speed. Most ASD’s have an output
monitor to report percentage of operation. A motor running at
50% uses 1/8 the energy of a motor running at 100%!
- Change out 50-watt incandescent exit lights with 1 - 5 watt
LED exit lights that last 25 years.
- Re-configure lighting and upgrade to energy efficient
fixtures if below current standards. The use of efficient
task lighting and less ceiling fixtures will save lighting
energy.
- Install electronic timers on parking lot lighting to turn off at a selected time rather than burning all night long. Allow sufficient lighting for safety and security.





